TRATOS® 6491B – H07Z
LSZH Conduit Wire

Now officially identified by the designations H07Z-U and H07Z-R, 6491B cables are also known by an old CMA Code 6491B. Cables designated “-U” have class 1 conductors, “-R” have class 2 conductors” flexible class 5 conductors designated “-K” are available on request. Tratos manufacture a complete range of cables with special fire performance for building and construction applications that are both safe and reliable when correctly selected, installed and properly used.
STANDARDS
- BS EN 50525-3-41 – Design
- BS EN 60228 – Conductor
- BS EN 50363-3 – Insulation
- BS EN 60332-1-2 – Test on single vertical cable
- BS EN 61034-2 – Smoke emission
- BS EN 50525-1 – Assessment of halogens for all non-metallic materials
- H07Z-R 1.5 mm2 to 6 mm2
Contact us:
Tel: +44 20 3148 5178
e-mail: sales@tratosgroup.com
Please don’t hesitate to contact us if you need additional information about our products.
Catalogues
Application
Suitable for power and lighting circuits and building wiring. Installed in surface mounted or embedded conduits, cable trunking or similar closed systems and for fixed protected installation in or on lighting fittings and inside appliances, switchgear and control gear. In particular for installation where fire, smoke emission and toxic fumes create a potential threat.CONSTRUCTION
- Conductors: BS EN 60228 Class 1 (H07Z-U) or Class 2 (H07Z-R) plain copper
- Insulation: Type EI5 polyolefin cross-linked, low smoke zero halogen (LSZH) material to EN 50363-5
- Insulation Colour: black, blue, brown, grey, orange, pink, red, turquoise, violet, white and green-and-yellow.
Standards
Technical Specifications
- Low voltage power
- Rated voltage 450/750 V
- NOTE 1 Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed installations with mechanical protection, within switchgear and control gear – see BS EN 50525-1.
- Maximum continuous conductor operating temperature 90 °C.
- Minimum installation temperatures 5 °C.
- Minimum operation temperature once installed – 15 °C.
- Maximum short circuit conductor temperature 250 °C, maximum duration of the fault current 5 s.
The tension applied to a cable should not exceed the values of tensile stress per conductor given below. This is subject to a total maximum tensile force of 1000 N.
- 50 N/mm2
during installation; - 15 N/mm2 for static tensile stress.
Minimum bending radius:
- ≤8 mm 4D
- >8 mm ≤12 mm 5D
- >12 mm 6D
Contact us
Please, don’t hesitate to contact us for additional information on our company or our products.
Related Case Studies
Other News
-
While others talk about Superconductors, CERN in Geneva uses Tratos, ICAS, and ENEA Superconductors
-
Tratos UK Ltd Achieves Strong EcoVadis Sustainability Rating
-
Tratos will showcase new products at TOC Europe 2025 after collecting major projects
-
Exploring Innovation in Fibre Optics: Students Visit Tratos Facilities in Italy
-
Tratos Sustainability Report 2023: Engineering a Sustainable Future with Innovation at its Core
-
Tratos Celebrates a Successful Showcase at Middle East Energy 2025
-
Tratos participates in the UKEF Supplier Fair on Cabinda International Airport
-
Powering a Connected, Resilient Future of Global Britain