Standard BS 6724 cables

TITLE: BS 6724 are Electric cables. Thermosetting insulated, armoured cables with rated voltages of 600/1 000 V and 1 900/3 300 V for fixed installations have low emissions of smoke and corrosive gases when affected by fire.

SCOPE:  BS6724 is a British Standard that specifies requirements for the construction and performance of thermosetting insulated, armoured cables of rated voltages of 600/1 000 V and 1 900/3 300 V, having low emission of smoke and corrosive gases when affected by fire. BS 6724 British Standard is applicable to cables for use in fixed installations in industrial areas, buildings or similar applications.

This British Standard specifies requirements for the following types of cables:

  • 600/1000 V cables, wire armoured and oversheathed having single-core, two-, three-, four- and five-core stranded copper conductor or 
  • 600/1000 V multicore auxiliary cables, wire armoured, and oversheathed, having 7, 12, 19, 27 and 37 core stranded copper conductors;
  • 1 900/3300 V cables, wire armoured and oversheathed, having single-core or three-core stranded copper conductors.

The cables specified in BS6724 standard are designed to have improved fire performance when installed in air and are expected to be used primarily in such locations. The cables are also suitable for direct burial in free-draining soil conditions but not in waterlogged soil or ground subject to flooding.

  • Note 1: Recommendations for the selection and operation of cables are given in Annex A. 
  • Note 2: Recommendations for the installation of cables are given in annex B. 
  • Note 3: Information to be provided with the enquiry or order is given in annex C.  

Construction

Conductor Plain annealed copper Class 1 or Class 2  (Circular or shaped)   Aluminium Class 1 
Insulation XLPE GP8 insulation
Core Identification Coloured or numbered for identification
Cores laid up In a continuous helix
Bedding Extruded layer of LSZH polymeric material
Armour Single Core Aluminum wire armour  
Armour Multicore Galvanised steel wire armour
Over sheath Extruded layer of LTS1 LSZH compound
Range of cables mm2
600/1000V Power

Single core 50 – 1000
Two core 1,5 – 400
Three core 1,5 – 400
Four core 1,5 – 400
Five core – 1,5 – 70

600/1000V multicore auxiliary

7,12,19,27, 37 and 48 core
In 1.5, 2.5 and 4 

1900/3300V Power

Single core 50 – 1000
Three core 16 – 400

BS 6724 Technical Specification.

Maximum continuous operating temperature 90oC
Maximum short circuit temperature 250 oC
Minimum installation temperature -15oC
MBR
Circular conductors 6D
Shaped conductors 8D

Products